Adept Response 12 Outlet Power Conditioner
and Audience powerChord
All measurements were done with a 4 wire test method using a
1.000 amp precision source as the test input.
DC resistance for input to output for the ground is 5.1 mohm at
the first outlet rising to 5.6 at the last one.
Measurement of the AC circuit resistance was done using a shorting
plug that measured .68 mohm. This amount is deducted from the
other measurements. All outlets were measured but not recorded
as they were all very close.
TEST RESULTS:
1) First outlet DC resistance loop back
from in to out = 29.09 mohm.
This is the same total resistance
that the AC power will see.
2) Last outlet measured 30.32 mohm
with all others falling in line between these 2 numbers.
3) Measurement with a 6' powerChord included
measured 43.4 mohms total.
The powerChord contributed only
7 mohm per leg.
|